Experiments have been performed to investigate the film-cooling characteristics with steam injection through one row (7 tubes) and two rows (13 tubes) of holes, inclined at an angle of 35 deg, over a flat plate. The spacing between the holes as well as the distance between the rows is 2 1/2 hole diameters. Data have been obtained for both steam and air film-cooling effectiveness at different axial and lateral locations downstream of the injection holes. The blowing rate M varied from 0.2 to 1.5. In the case of one-row injection, the results show that the film-cooling effectiveness with steam injection is about 50 to 100 percent higher than that with air injection at downstream locations, depending upon the blowing rate; however, the increase in film-cooling effectiveness is reduced near the injection hole region at high blowing rates. In the case of two-row injection, the laterally averaged film cooling effectiveness η can be correlated with the two-dimensional film-cooling parameter ξ. The η with steam injection is about 80 to 100 percent higher than that with air injection at low blowing rates and/or at downstream locations (ξ ≥ 15). However, the increase in η with steam injection is reduced near the injection hole region and/or at high blowing rates (ξ ≤ 15).
Skip Nav Destination
Article navigation
July 1986
Research Papers
Flat-Plate Film Cooling With Steam Injection Through One Row and Two Rows of Inclined Holes
J. C. Han,
J. C. Han
Turbomachinery Laboratories, Department of Mechanical Engineering, Texas A&M University, College Station, TX 77843
Search for other works by this author on:
A. B. Mehendale
A. B. Mehendale
Turbomachinery Laboratories, Department of Mechanical Engineering, Texas A&M University, College Station, TX 77843
Search for other works by this author on:
J. C. Han
Turbomachinery Laboratories, Department of Mechanical Engineering, Texas A&M University, College Station, TX 77843
A. B. Mehendale
Turbomachinery Laboratories, Department of Mechanical Engineering, Texas A&M University, College Station, TX 77843
J. Turbomach. Jul 1986, 108(1): 137-144 (8 pages)
Published Online: July 1, 1986
Article history
Received:
January 20, 1986
Online:
November 9, 2009
Citation
Han, J. C., and Mehendale, A. B. (July 1, 1986). "Flat-Plate Film Cooling With Steam Injection Through One Row and Two Rows of Inclined Holes." ASME. J. Turbomach. July 1986; 108(1): 137–144. https://doi.org/10.1115/1.3262013
Download citation file:
Get Email Alerts
Evaluating Thin-Film Thermocouple Performance on Additively Manufactured Turbine Airfoils
J. Turbomach (July 2025)
Thermohydraulic Performance and Flow Structures of Diamond Pyramid Arrays
J. Turbomach (July 2025)
Related Articles
Combined Effects of Freestream Pressure Gradient and Density Ratio on the Film Cooling Effectiveness of Round and Shaped Holes on a Flat Plate
J. Turbomach (April,2017)
The Effect of Internal Crossflow on the Adiabatic Effectiveness of Compound Angle Film Cooling Holes
J. Turbomach (July,2015)
A Detailed Study of the Interaction Between Two Rows of Cooling Holes
J. Turbomach (April,2018)
Experimental Study of Effusion Cooling With Pressure-Sensitive Paint
J. Eng. Gas Turbines Power (May,2017)
Related Chapters
Members in Bending
Design & Analysis of ASME Boiler and Pressure Vessel Components in the Creep Range
Flat Plates, Covers, and Flanges
Guidebook for the Design of ASME Section VIII Pressure Vessels
Finite Element Solution of Natural Convection Flow of a Nanofluid along a Vertical Flat Plate with Streamwise Sinusoidal Surface Temperature
International Conference on Computer and Electrical Engineering 4th (ICCEE 2011)