This paper develops a four-parameter change-point model of energy consumption as a function of dry-bulb temperature, along with accompanying error diagnostics for the model’s parameters. The model is a generalization of the widely used three-parameter, or variable-base degree-day method. The model is applied to data from a case study grocery store, is compared to the three-parameter PRISM CO model of the store data, and is shown to provide a statistically better fit to consumption data below about 15°C. This model appears to be useful for diagnosing unexpected energy use in some buildings and should be useful for determining retrofit energy savings from monitored pre-retrofit and post-retrofit data for the class of buildings whose pre-retrofit consumption is fit by a four-parameter linear change-point model.
Skip Nav Destination
Article navigation
May 1992
Research Papers
A Four-Parameter Change-Point Model for Predicting Energy Consumption in Commercial Buildings
David Ruch,
David Ruch
Mechanical Engineering Department, Texas A&M University, College Station, 77843
Search for other works by this author on:
David E. Claridge
David E. Claridge
Mechanical Engineering Department, Texas A&M University, College Station, 77843
Search for other works by this author on:
David Ruch
Mechanical Engineering Department, Texas A&M University, College Station, 77843
David E. Claridge
Mechanical Engineering Department, Texas A&M University, College Station, 77843
J. Sol. Energy Eng. May 1992, 114(2): 77-83 (7 pages)
Published Online: May 1, 1992
Article history
Received:
January 1, 1991
Revised:
July 1, 1991
Online:
June 6, 2008
Citation
Ruch, D., and Claridge, D. E. (May 1, 1992). "A Four-Parameter Change-Point Model for Predicting Energy Consumption in Commercial Buildings." ASME. J. Sol. Energy Eng. May 1992; 114(2): 77–83. https://doi.org/10.1115/1.2929993
Download citation file:
Get Email Alerts
Mass Flow Control Strategy for Maximum Energy Extraction in Thermal Energy Storage Tanks
J. Sol. Energy Eng (December 2025)
Related Articles
A Change-Point Principal Component Analysis (CP/PCA) Method for Predicting Energy Usage in Commercial Buildings: The PCA Model
J. Sol. Energy Eng (May,1993)
Development of Graphical Indices for Viewing Building Energy Data: Part I
J. Sol. Energy Eng (August,1998)
The Sub-Metered HVAC Implemented for Demand Response Dataset
J. Dyn. Sys., Meas., Control (January,2024)
Closed-Form Correlation of Buildings Energy Use With Key Design Parameters Calibrated Using a Genetic Algorithm
J. Sol. Energy Eng (November,2011)
Related Chapters
Dynamic Cool Roofing Systems
Advanced Energy Efficient Building Envelope Systems
Energy Consumption Simulation and Energy Conservation Measures for Typical Public Buildings in Chengdu
International Conference on Green Buildings and Optimization Design (GBOD 2012)
The Design and Implement of Remote Inclinometer for Power Towers Based on MXA2500G/GSM
International Conference on Mechanical and Electrical Technology, 3rd, (ICMET-China 2011), Volumes 1–3