This paper presents the results of an experimentally validated computational fluid dynamics (CFD) model for a data center with fully implemented fan curves on both the servers and the computer room air conditioner (CRAC). Both open and contained cold aisle systems are considered in this study. This work is divided into sections for the baseline system (prior to installing containment) calibration and the fully contained cold aisle system calibration and leakage characterization. In the open system, the fan curve of the CRAC unit is extracted from the manufacturer data, while the fan curve of the load banks is obtained through experimental measurements. The experimental results are found to be in good agreement with the average model predictions. In the fully contained cold aisle system, a detailed containment CFD model is developed based on experimental measurements. The model is validated by comparing the flow rate through the perforated floor tiles and the rack inlet temperatures with the experimental measurements. The CFD results are found to be in good agreement with the experimental data with an average relative error between the measured and computed flow rate of approximately 6.7%. Temperature measurements are used to calibrate the sources of leakage in the containment and rack mounting rails. The temperature measurements and the CFD results agree well with an average difference of less than 1 °C. This study provides important modeling guidelines for data centers. In order to predict the performance of contained cold aisle systems flow distribution, it is crucial that physics based models of fan curves, server internal resistances, detailed rack models, and other design details are all accurate and experimentally verified.
Skip Nav Destination
Article navigation
June 2015
Research-Article
Experimentally Validated Computational Fluid Dynamics Model for a Data Center With Cold Aisle Containment
Sami A. Alkharabsheh,
Sami A. Alkharabsheh
1
Department of Mechanical Engineering,
State University of New York,
e-mail: salkhar1@binghamton.edu
Binghamton University
,State University of New York,
Binghamton, NY 13902
e-mail: salkhar1@binghamton.edu
1Corresponding author.
Search for other works by this author on:
Bahgat G. Sammakia,
Bahgat G. Sammakia
Department of Mechanical Engineering,
State University of New York,
Binghamton University
,State University of New York,
Binghamton, NY 13902
Search for other works by this author on:
Saurabh K. Shrivastava
Saurabh K. Shrivastava
PANDUIT Corporation
,Panduit Dr.
,Tinley Park, IL 60487
Search for other works by this author on:
Sami A. Alkharabsheh
Department of Mechanical Engineering,
State University of New York,
e-mail: salkhar1@binghamton.edu
Binghamton University
,State University of New York,
Binghamton, NY 13902
e-mail: salkhar1@binghamton.edu
Bahgat G. Sammakia
Department of Mechanical Engineering,
State University of New York,
Binghamton University
,State University of New York,
Binghamton, NY 13902
Saurabh K. Shrivastava
PANDUIT Corporation
,Panduit Dr.
,Tinley Park, IL 60487
1Corresponding author.
Contributed by the Electronic and Photonic Packaging Division of ASME for publication in the JOURNAL OF ELECTRONIC PACKAGING. Manuscript received February 11, 2014; final manuscript received December 5, 2014; published online January 21, 2015. Assoc. Editor: Madhusudan Iyengar.
J. Electron. Packag. Jun 2015, 137(2): 021010 (9 pages)
Published Online: June 1, 2015
Article history
Received:
February 11, 2014
Revision Received:
December 5, 2014
Online:
January 21, 2015
Citation
Alkharabsheh, S. A., Sammakia, B. G., and Shrivastava, S. K. (June 1, 2015). "Experimentally Validated Computational Fluid Dynamics Model for a Data Center With Cold Aisle Containment." ASME. J. Electron. Packag. June 2015; 137(2): 021010. https://doi.org/10.1115/1.4029344
Download citation file:
Get Email Alerts
Impact of Encapsulated Phase Change Material Additives for Improved Thermal Performance of Silicone Gel Insulation
J. Electron. Packag (December 2024)
Special Issue on InterPACK2023
J. Electron. Packag
Extreme Drop Durability of Sintered Silver Traces Printed With Extrusion and Aerosol Jet Processes
J. Electron. Packag (December 2024)
Related Articles
Experimental and Computational Investigations of the Thermal Environment in a Small Operational Data Center for Potential Energy Efficiency Improvements
J. Electron. Packag (September,2020)
Experimental Characterization of Various Cold Aisle Containment Configurations for Data Centers
J. Electron. Packag (March,2015)
Experimental and Numerical Analysis of Data Center Pressure and Flow Fields Induced by Backward and Forward CRAH Technology
J. Electron. Packag (September,2022)
Airflow and Cooling in a Data Center
J. Heat Transfer (July,2010)
Related Proceedings Papers
Related Chapters
Insights and Results of the Shutdown PSA for a German SWR 69 Type Reactor (PSAM-0028)
Proceedings of the Eighth International Conference on Probabilistic Safety Assessment & Management (PSAM)
PSA Level 2 — NPP Ringhals 2 (PSAM-0156)
Proceedings of the Eighth International Conference on Probabilistic Safety Assessment & Management (PSAM)
Iwe and Iwl
Companion Guide to the ASME Boiler and Pressure Vessel Code, Volume 2, Fourth Edition