Skip to Main Content
ASME Press Select Proceedings

International Symposium on Information Engineering and Electronic Commerce, 3rd (IEEC 2011)

Editor
C. B. Povloviq
C. B. Povloviq
National Technical University of Ukraine
Search for other works by this author on:
C. W. Lu
C. W. Lu
Huangshi Institute of Technology
Search for other works by this author on:
ISBN:
9780791859759
No. of Pages:
562
Publisher:
ASME Press
Publication date:
2011

Very fast transient overvoltage (VFTO) may cause damage to the insulation of electric equipments in gas insulated substations. It is generated by multi-reignitions between the contacts of disconnector, when the disconnector is closing or opening. So it is important to calculate the VFTOs caused by multi-reignitions of disconnector. In this paper, it is pointed out that there is a linear relationship between the VFTOs originated by the previous multi-reignitions when the disconnector is closing or the last multi-reignitions when the disconnector is opening. Combined this conclusion with the phenomenon of multi-reignitions, the VFTOs caused by multi-reignitions are calculated. Finally, the influence of voltage phase at which the disconnector begins to close or open to all amplitudes of all VFTOs caused by multi-reignitions is analyzed. It shows that there is a minimum value of the maximum amplitudes of VFTOs when the disconnector works at a correct range of voltage phase and when the disconnector closes under a condition that the residual voltage on no-load bus is close to 0.