Condensation in Exterior Building Wall Systems
By
Bruce S. Kaskel
Bruce S. Kaskel
1
Wiss, Janney, Elstner Associates, Inc.
,
10 S. LaSalle Street, Chicago, IL
Search for other works by this author on:
Robert J. Kudder
Robert J. Kudder
2
Raths, Raths & Johnson, Inc.
,
835 Midway Drive, Willowbrook, IL
Search for other works by this author on:
ISBN:
978-0-8031-4471-2
No. of Pages:
327
Publisher:
ASTM International
Publication date:
2011

An electronics manufacturing facility in Colorado was constructed with typical commercial steel framing containing fiberglass batt insulation with foil-facing as the vapor retarder. A large portion of the facility required constant positive space pressurization and an indoor relative humidity (RH) of 48 % RH at 21°C (70°F). Due to a lack of containment of the moist interior air, condensation formed in the exterior walls, in the roofing, on the window and door systems, and on the skylights of the facility, particularly along the north and east elevations of the building, which resulted in significant damage to the wall components and the inability of the HVAC system to remain properly balanced. The as-constructed exterior wall systems were evaluated for performance relative to the existing building mechanical system. It was determined that the as-designed and as-constructed exterior wall assemblies and components could not perform satisfactorily under the necessary indoor environmental requirements. Options were explored to improve the performance of the exterior wall assemblies and related details. Due to a number of constraints, it was decided that constructing new walls inside the as-constructed exterior walls and windows, thereby creating an “interstitial” space to separate the exterior walls from the interior building space for their full height and mechanically supplying warm, dry air to this interstitial space, was the desired method to correct the condensation problems that were occurring. These repairs have proven to be effective. This paper discusses the original design and construction, the method of evaluation of the condensation problems that occurred, and the design and results of the implemented repairs.

1.
99% Winter Design Dry Bulb Temperature
,”
Handbook of Fundamentals
,
American Society of Heating, Refrigerating and Air Conditioning Engineers, Inc. (ASHRAE)
,
Denver, CO
,
1972
, Chap. 33, Table 1.
2.
97.5% Winter Design Dry Bulb Temperature
,”
Handbook of Fundamentals
,
American Society of Heating, Refrigerating and Air Conditioning Engineers, Inc. (ASHRAE)
,
Denver, CO
,
1972
, Chap. 33, Table 1.
3.
AAMA 1503-98,
2004
, “
Voluntary Test Method for Thermal Transmittance and Condensation Resistance of Windows, Doors, and Glazed Wall Section
,”
American Architectural Manufacturers Association (AAMA)
,
Schaumburg, IL
, Fig. 14.
This content is only available via PDF.
You do not currently have access to this chapter.
Close Modal

or Create an Account

Close Modal
Close Modal