Skip to Main Content
Skip Nav Destination
ASTM Selected Technical Papers
Corrosion Effect of Stray Currents and the Techniques for Evaluating Corrosion of Rebars in Concrete
By
V Chaker
V Chaker
1
Gilbert/Commonwealth, Inc.
,
Reading, PA 19603
;
Symposium chairman and editor
.
Search for other works by this author on:
ISBN-10:
0-8031-0468-5
ISBN:
978-0-8031-0468-6
No. of Pages:
151
Publisher:
ASTM International
Publication date:
1985

Prestressed concrete cylinder pipe (PCCP) is constructed by circumferentially winding a high strength steel wire, under tension, around a concrete core containing a sheet steel cylinder, which serves as a watertight membrane. The service life of such pipe is generally determined by the ability of this steel prestressing wire to retain its integrity under tension. Corrosion of the steel wire results in pitting, embrittlement, or the dissolution of the iron with a corresponding reduction in cross-sectional area. The result is degradation of the physical strength of the high tensile wire and possible failure of the prestressed concrete cylinder pipe through this mechanism. Pipe affected by this failure mode does not develop leaks as in the case of the steel pipe, but bursts catastrophically. Failure is usually attributed to “wire breaks,” not specifically to corrosion.

For concrete cylinder pipe, the components of the joint are susceptible to stray current corrosion if component low resistance continuity does not exist. This condition can be responsible for failure of the steel prestressing wires if they are not electrically continuous with the other components of the pipe (steel cylinder, bell ring, spigot ring, fittings, and so forth).

This paper presents the potential corrosion problems and causes associated with the metallic components of prestressed concrete cylinder pipe. The difficulties in detecting these problems, because of materials and fabrication practices are discussed, as well as methods that have been used successfully to detect corrosion in buried lines (pipe-to-soil potential profiles, cell-to-cell potential profiles).

The results of a few typical studies are presented as a suggested approach to the investigation and analysis of potential problems involving both galvanic and electrolytic (stray current) corrosion.

1.
American Water Works Association
,
AWWA Standard for Prestressed Concrete Pressure Pipe, Steel Cylinder Type, for Water and Other Liquids
, AWWA C 301-79,
28
11
1979
.
2.
Husock
,
B.
, “
Fundamentals of Cathodic Protection
,” Harco Corporation Paper
HC-4
, paper prepared for presentation at
AIEE Joint Southwest and Mid-America District Meeting
,
St. Louis, MO
, 30 April–2 May 1962.
3.
Phillips
,
E.
, “
Survey of Corrosion of Prestressing Steel in Concrete Water-retaining Structures
,” Australian Water Resources Council, Technical Papers, No.
9
,
Canberra
,
Australian Government Publishing Service
,
1975
.
4.
Klodt
,
D. T.
, “
Studies of Electrochemical Corrosion and Brittle Fracture Susceptibility of Prestressing Steel in Relation to Prestressed Concrete Bridges
,”
National Association of Corrosion Engineers
,
Houston, TX
,
1969
, p. 5.
This content is only available via PDF.
You do not currently have access to this chapter.
Close Modal

or Create an Account

Close Modal
Close Modal