CFD simulation was carried out to corroborate experimental data at fixed heat load of nominally 2.3kW from a natural draft heat exchanger of face dimensions of 0.75m × 0.75m, with or without mitigation of the cold inflow at the chimney exit, where mitigation by installing wire mesh on top of the chimney has been shown by the experiments to enhance air flow rate. A chimney model was simulated at fixed heat loads in a still surrounding at ambient temperature of 30 degree Celsius and atmospheric pressure for two modes: Mode 1 and Mode 0 for with and without a flow resistor (wire mesh) respectively at the top exit. It was found that the simulation could reproduce most of the trends of the experimental data, but had a tendency to magnify the detrimental effects of cold inflow and exaggerate the remedial action of wire mesh in preventing cold inflow, as reflected by the ratio of Mode 1 to Mode 0 air mass flowrate by a factor of up to 2.36, compared to 1.50 in the experimental data. In both simulation and experiment, the average air flow rates obtained at chimney heights of 0.35m, 0.65m, 0.95m and 1.25m, showed progressive increase of air mass flow rate for all cases. Both experimental and simulated heat gain in Mode 0 were more or less constant until the highest chimney height where they showed apparent breakout upwards, whereas in Mode 1 the experimental heat gains gently reduced to a plateau while the simulated heat gains hovered at around 2.3kW. The back calculated values of Mode 0 experimental outlet temperature at between 140 to 240°C raises concern of hotspot in some electronic components by the ineffectiveness of chimney systems without cold inflow mitigation. Further experiments of similar scale with steadier control of heat flux and heating temperature, and simulating with other turbulence models in transient mode will improve understanding in both Mode 0 and Mode 1 of operation.
Skip Nav Destination
ASME 2015 Power Conference collocated with the ASME 2015 9th International Conference on Energy Sustainability, the ASME 2015 13th International Conference on Fuel Cell Science, Engineering and Technology, and the ASME 2015 Nuclear Forum
June 28–July 2, 2015
San Diego, California, USA
Conference Sponsors:
- Power Division
ISBN:
978-0-7918-5660-4
PROCEEDINGS PAPER
CFD Simulation and Experimental Data for a Fixed Heat Load Natural Draft Air-Cooled Heat Exchanger With Cold Inflow Mitigation
Christopher C. M. Chu,
Christopher C. M. Chu
Universiti Malaysia Sabah, Kota Kinabalu, Sabah, Malaysia
Search for other works by this author on:
Md. Mizanur Rahman,
Md. Mizanur Rahman
Universiti Malaysia Sabah, Kota Kinabalu, Sabah, Malaysia
Search for other works by this author on:
Sivakumar Kumaresan
Sivakumar Kumaresan
Universiti Malaysia Sabah, Kota Kinabalu, Sabah, Malaysia
Search for other works by this author on:
Christopher C. M. Chu
Universiti Malaysia Sabah, Kota Kinabalu, Sabah, Malaysia
Md. Mizanur Rahman
Universiti Malaysia Sabah, Kota Kinabalu, Sabah, Malaysia
Sivakumar Kumaresan
Universiti Malaysia Sabah, Kota Kinabalu, Sabah, Malaysia
Paper No:
POWER2015-49020, V001T12A001; 6 pages
Published Online:
October 27, 2015
Citation
Chu, CCM, Rahman, MM, & Kumaresan, S. "CFD Simulation and Experimental Data for a Fixed Heat Load Natural Draft Air-Cooled Heat Exchanger With Cold Inflow Mitigation." Proceedings of the ASME 2015 Power Conference collocated with the ASME 2015 9th International Conference on Energy Sustainability, the ASME 2015 13th International Conference on Fuel Cell Science, Engineering and Technology, and the ASME 2015 Nuclear Forum. ASME 2015 Power Conference. San Diego, California, USA. June 28–July 2, 2015. V001T12A001. ASME. https://doi.org/10.1115/POWER2015-49020
Download citation file:
13
Views
Related Proceedings Papers
Related Articles
Experimental Validation of ANSYS CFX for Transient Flows With Heat Transfer in a Tubular Heat Exchanger
ASME J of Nuclear Rad Sci (April,2020)
Conjugated Periodic Turbulent Forced Convection in a Parallel Plate Channel
J. Heat Transfer (February,1994)
Related Chapters
Threshold Functions
Closed-Cycle Gas Turbines: Operating Experience and Future Potential
Experimental Investigation of an Improved Thermal Response Test Equipment for Ground Source Heat Pump Systems
Inaugural US-EU-China Thermophysics Conference-Renewable Energy 2009 (UECTC 2009 Proceedings)
Numerical Simulation Research on a Fixed Bed Gasifier
International Conference on Information Technology and Management Engineering (ITME 2011)