The high restrictions in environmental requirements have led to modifications of the both coal type and firing mode. In order to prevent a different faults in boiler operation and as a result a reliability reduction, special monitoring and diagnostic techniques is required for engineering analysis and utility production management. In this sense an on-line supervision system FURNACE have developed and implemented for 575, 550, 360 Mw coal fired units. The developed system provides on-line information regards furnace performance, including fireball location, furnace exit temperature increase that indicates the necessity of activate furnace sootblowers to control steam temperatures and prevent excessive accumulations of slag and heat surfaces tube overheating. However, the FURNACE system can not provide flue gas temperature distribution near the burner zone and it leads to limitation of the possibility of furnace fine tuning for the aim of NOx reduction. Due to this reason new diagnostic system ORFEUS was installed in power plant. The ORFEUS is a system for continuous visual monitoring of high temperature processes with a sensor lance. A high quality picture with wide angle of view and a small sensor diameter is achieved using a boroskope as lens. With this technology the CCD camera can be mounted in the cold part of the lance. This way sensitive equipment is mounted outside the combustion chamber, allowing continuous use with high process temperatures. The pictures coming from the sensor can be viewed and analyzed directly in the control room. In order to evaluate capability of both system combined application series of tests with different operation were conducted on the boiler. The testing was primarily focused on quantifying the impact of overfire air (OFA), excess air, primary air flow and unit loads on boiler, furnace, pulverizers performance, NOx and unburned carbon loss etc. The evaluation was performed for 575 MW units equipped with tangentially fired boilers designed by Combustion Engineering. The on-line information obtained from both FURNACE and ORFEUS systems is allowed us to perform fine tuning of the firing system in order to optimize combustion process. Based on performed work may be concluded that combination of both system is able us to receive detail information of furnace performance in real time including flame position in the initial burner zone. As result it was achieved additional NOx reduction by 10–15% at unit full load and by 20–35% at partial load without any impact on boiler performance, efficiency and reliability.
Skip Nav Destination
ASME 2009 Power Conference
July 21–23, 2009
Albuquerque, New Mexico, USA
Conference Sponsors:
- Power Division
ISBN:
978-0-7918-4350-5
PROCEEDINGS PAPER
Combination of Advanced Supervision System FURNACE With Continues Visual Monitoring ORFEUS for Proper On-Line Performance Analysis of the Furnace Firing Coal in Large Utility Boilers
B. Chudnovsky,
B. Chudnovsky
Israel Electric Corporation, Haifa, Israel
Search for other works by this author on:
A. Talanker,
A. Talanker
Israel Electric Corporation, Haifa, Israel
Search for other works by this author on:
B. Kogan,
B. Kogan
Israel Electric Corporation, Haifa, Israel
Search for other works by this author on:
M. Daniliuc,
M. Daniliuc
Israel Electric Corporation, Haifa, Israel
Search for other works by this author on:
L. Frega
L. Frega
Orfeus Combustion Engineering GmbH, Hamburg, Germany
Search for other works by this author on:
B. Chudnovsky
Israel Electric Corporation, Haifa, Israel
A. Talanker
Israel Electric Corporation, Haifa, Israel
B. Kogan
Israel Electric Corporation, Haifa, Israel
M. Daniliuc
Israel Electric Corporation, Haifa, Israel
S. Lev
Israel Electric Corporation, Haifa, Israel
L. Frega
Orfeus Combustion Engineering GmbH, Hamburg, Germany
Paper No:
POWER2009-81017, pp. 1-8; 8 pages
Published Online:
September 22, 2010
Citation
Chudnovsky, B, Talanker, A, Kogan, B, Daniliuc, M, Lev, S, & Frega, L. "Combination of Advanced Supervision System FURNACE With Continues Visual Monitoring ORFEUS for Proper On-Line Performance Analysis of the Furnace Firing Coal in Large Utility Boilers." Proceedings of the ASME 2009 Power Conference. ASME 2009 Power Conference. Albuquerque, New Mexico, USA. July 21–23, 2009. pp. 1-8. ASME. https://doi.org/10.1115/POWER2009-81017
Download citation file:
6
Views
Related Proceedings Papers
Related Articles
Two-Dimensional Spectroscopic Observation of Nonluminous Flames in a Regenerative Industrial Furnace Using Coal Gas
J. Eng. Gas Turbines Power (January,2004)
External Corrosion of Furnace-Wall Tubes—I History and Occurrence
Trans. ASME (May,1945)
Related Chapters
Combined Cycle Power Plant
Energy and Power Generation Handbook: Established and Emerging Technologies
The Impact of Plant Economics on the Design of Industrial Energy Systems
Industrial Energy Systems
Introduction
Consensus on Operating Practices for Control of Water and Steam Chemistry in Combined Cycle and Cogeneration