Modern day data centers are operated at high power for increased power density, maintenance, and cooling which covers almost 2 percent (70 billion kilowatt-hours) of the total energy consumption in the US. IT components and cooling system occupy the major portion of this energy consumption. Although data centers are designed to perform efficiently, cooling the high-density components is still a challenge. So, alternative methods to improve the cooling efficiency has become the drive to reduce the cooling cost. As liquid cooling is more efficient for high specific heat capacity, density, and thermal conductivity, hybrid cooling can offer the advantage of liquid cooling of high heat generating components in the traditional air-cooled servers. In this experiment, a 1U server is equipped with cold plate to cool the CPUs while the rest of the components are cooled by fans. In this study, predictive fan and pump failure analysis are performed which also helps to explore the options for redundancy and to reduce the cooling cost by improving cooling efficiency. Redundancy requires the knowledge of planned and unplanned system failures. As the main heat generating components are cooled by liquid, warm water cooling can be employed to observe the effects of raised inlet conditions in a hybrid cooled server with failure scenarios. The ASHRAE guidance class W4 for liquid cooling is chosen for our experiment to operate in a range from 25°C – 45°C. The experiments are conducted separately for the pump and fan failure scenarios. Computational load of idle, 10%, 30%, 50%, 70% and 98% are applied while powering only one pump and the miniature dry cooler fans are controlled externally to maintain constant inlet temperature of the coolant. As the rest of components such as DIMMs & PCH are cooled by air, maximum utilization for memory is applied while reducing the number fans in each case for fan failure scenario. The components temperatures and power consumption are recorded in each case for performance analysis.
Skip Nav Destination
ASME 2017 International Technical Conference and Exhibition on Packaging and Integration of Electronic and Photonic Microsystems collocated with the ASME 2017 Conference on Information Storage and Processing Systems
August 29–September 1, 2017
San Francisco, California, USA
Conference Sponsors:
- Electronic and Photonic Packaging Division
ISBN:
978-0-7918-5809-7
PROCEEDINGS PAPER
Characterization of an Isolated Hybrid Cooled Server With Failure Scenarios Using Warm Water Cooling
Uschas Chowdhury,
Uschas Chowdhury
University of Texas at Arlington, Arlington, TX
Search for other works by this author on:
Manasa Sahini,
Manasa Sahini
University of Texas at Arlington, Arlington, TX
Search for other works by this author on:
Ashwin Siddarth,
Ashwin Siddarth
University of Texas at Arlington, Arlington, TX
Search for other works by this author on:
Dereje Agonafer,
Dereje Agonafer
University of Texas at Arlington, Arlington, TX
Search for other works by this author on:
Steve Branton
Steve Branton
Data Center Solution at ASETEK, San Jose, CA
Search for other works by this author on:
Uschas Chowdhury
University of Texas at Arlington, Arlington, TX
Manasa Sahini
University of Texas at Arlington, Arlington, TX
Ashwin Siddarth
University of Texas at Arlington, Arlington, TX
Dereje Agonafer
University of Texas at Arlington, Arlington, TX
Steve Branton
Data Center Solution at ASETEK, San Jose, CA
Paper No:
IPACK2017-74028, V001T02A002; 7 pages
Published Online:
October 27, 2017
Citation
Chowdhury, U, Sahini, M, Siddarth, A, Agonafer, D, & Branton, S. "Characterization of an Isolated Hybrid Cooled Server With Failure Scenarios Using Warm Water Cooling." Proceedings of the ASME 2017 International Technical Conference and Exhibition on Packaging and Integration of Electronic and Photonic Microsystems collocated with the ASME 2017 Conference on Information Storage and Processing Systems. ASME 2017 International Technical Conference and Exhibition on Packaging and Integration of Electronic and Photonic Microsystems. San Francisco, California, USA. August 29–September 1, 2017. V001T02A002. ASME. https://doi.org/10.1115/IPACK2017-74028
Download citation file:
19
Views
Related Proceedings Papers
Related Articles
Efficiency Improvement of Photovoltaic Solar Modules by Cooling Using an Underground Heat Exchanger
J. Sol. Energy Eng (December,2022)
Application of Controllable Electric Coolant Pump for Fuel Economy and Cooling Performance Improvement
J. Eng. Gas Turbines Power (January,2007)
Steady State and Transient Experimentally Validated Analysis of Hybrid Data Centers
J. Electron. Packag (June,2015)
Related Chapters
Insights and Results of the Shutdown PSA for a German SWR 69 Type Reactor (PSAM-0028)
Proceedings of the Eighth International Conference on Probabilistic Safety Assessment & Management (PSAM)
Studies Performed
Closed-Cycle Gas Turbines: Operating Experience and Future Potential
Comparison of the Availability of Trip Systems for Reactors with Exothermal Reactions (PSAM-0361)
Proceedings of the Eighth International Conference on Probabilistic Safety Assessment & Management (PSAM)