It is now common for data center managers to question the impact on server energy usage of two recent impact factors: (1) the rise in the data center inlet air temperature to servers per 2008 ASHRAE guidelines, and (2) the fan speed increase from the use of rack level heat exchangers such as Rear Door Heat Exchangers. To help acquire a deeper understanding of the relevant issues, a system floor thermal test was built on the IBM New York data center benchmark floor which consisted of a standard 19″ rack filled with 39 3.0 GHz 1U servers that dissipated between 10–17 kW depending on extent of server utilization. Fan speed, chip temperature metrics, and server power data was collected using product debug codes and server level programs. A simulated air heat load was installed right in front of this server rack to allow the manipulation of air inlet temperature into the servers from 20 °C to 32 °C. Two different rack level configurations were considered for the experiments: (i) a perforated front door and no door at the rear, and (ii) a perforated front door and a Rear Door Heat Exchanger at the rear. An exerciser program was used to vary the CPU utilization from Idle to 70% which represented a typical data center work load. Data was collected for 19 servers of the 39 servers (remaining were in use by Benchmark Lab) for the two rack configurations, for 4 inlet server air temperatures, and for two chip exerciser settings, i.e. 16 experiments. For the 70% exerciser setting (typical operation) and the base line rack configuration without rack level heat exchangers, the rise in server power for an increase in inlet air temperature was 5.2% for the 20 °C to 27 °C change and was 17% for the 20 °C to 31 °C change. For the 70% exerciser setting (typical), the increase in server power from the use of rack level heat exchangers (Rear Door Heat Exchanger) was less than 1.3% for all the conditions. Given the broad range of fan speed algorithms and cooling hardware in server products on the market and their change over each generation, significant further study will be required to characterize each category of systems for these conditions. However, the present study provides a template for quantifying server energy usage in a context that data center managers can understand and use.
Skip Nav Destination
ASME 2011 Pacific Rim Technical Conference and Exhibition on Packaging and Integration of Electronic and Photonic Systems
July 6–8, 2011
Portland, Oregon, USA
Conference Sponsors:
- Electronic and Photonic Packaging Division
ISBN:
978-0-7918-4462-5
PROCEEDINGS PAPER
Experimental Characterization of Server Rack Energy Use at Elevated Ambient Temperatures
Madhusudan Iyengar,
Madhusudan Iyengar
IBM, Poughkeepsie, NY
Search for other works by this author on:
Vinod Kamath,
Vinod Kamath
IBM, Research Triangle Park, NC
Search for other works by this author on:
Bejoy Kochuparambil
Bejoy Kochuparambil
IBM, Research Triangle Park, NC
Search for other works by this author on:
Madhusudan Iyengar
IBM, Poughkeepsie, NY
Roger Schmidt
IBM, Poughkeepsie, NY
Vinod Kamath
IBM, Research Triangle Park, NC
Bejoy Kochuparambil
IBM, Research Triangle Park, NC
Paper No:
IPACK2011-52207, pp. 617-622; 6 pages
Published Online:
February 14, 2012
Citation
Iyengar, M, Schmidt, R, Kamath, V, & Kochuparambil, B. "Experimental Characterization of Server Rack Energy Use at Elevated Ambient Temperatures." Proceedings of the ASME 2011 Pacific Rim Technical Conference and Exhibition on Packaging and Integration of Electronic and Photonic Systems. ASME 2011 Pacific Rim Technical Conference and Exhibition on Packaging and Integration of Electronic and Photonic Systems, MEMS and NEMS: Volume 2. Portland, Oregon, USA. July 6–8, 2011. pp. 617-622. ASME. https://doi.org/10.1115/IPACK2011-52207
Download citation file:
15
Views
Related Proceedings Papers
Related Articles
New Thermal Management Systems for Data Centers
J. Thermal Sci. Eng. Appl (September,2012)
Too Hot for Comfort
Mechanical Engineering (December,2006)
Steady State and Transient Experimentally Validated Analysis of Hybrid Data Centers
J. Electron. Packag (June,2015)
Related Chapters
Study on the Energy-Saving Technologies and Methods of Green Building
International Conference on Mechanical and Electrical Technology, 3rd, (ICMET-China 2011), Volumes 1–3
A Balance-Space-Based Operation Strategy for CCHP Systems
Combined Cooling, Heating, and Power Systems: Modelling Optimization, and Operation
Control and Operational Performance
Closed-Cycle Gas Turbines: Operating Experience and Future Potential