The work presented in this paper describes a simplified thermodynamic model that can be used for exploring optimization possibilities in air-cooled data centers. The model has been used to identify optimal, energy-efficient designs, operating scenarios, and operating parameters such as flow rates and air supply temperature. The model is used to parametrically evaluate the total energy consumption of the data center cooling infrastructure, by considering changes in the server temperature rise. The results of this parametric analysis highlight the important features that need to be considered when optimizing the operation of air-cooled data centers, especially the trade-off between low air supply temperature and increased air flow rate. The analysis is used to elucidate the deleterious effect of temperature non-uniformity at the inlet of the racks on the data center cooling infrastructure power consumption. A recirculation non-uniformity metric, θ, is introduced, which is the ratio of the maximum recirculation of any server to the average recirculation of all servers. The analysis of open-aisle data centers shows that as the recirculation non-uniformity at the inlet of the racks increases, optimal operation tends toward lower recirculation and higher power consumption; stressing the importance of providing as uniform conditions to the racks as possible. Cooling infrastructure energy savings greater than 40% are possible for a data center with uniform recirculation (θ = 0) compared to a data center with a typical recirculation non-uniformity (θ = 4). It is also revealed that servers with a modest temperature rise (∼10°C) have a wider latitude for cooling optimization than those with a high temperature rise (≥20°C).
Skip Nav Destination
ASME 2011 Pacific Rim Technical Conference and Exhibition on Packaging and Integration of Electronic and Photonic Systems
July 6–8, 2011
Portland, Oregon, USA
Conference Sponsors:
- Electronic and Photonic Packaging Division
ISBN:
978-0-7918-4462-5
PROCEEDINGS PAPER
Energy Modeling of Air-Cooled Data Centers: Part II—The Effect of Recirculation on the Energy Optimization of Open-Aisle, Air-Cooled Data Centers
Dustin W. Demetriou,
Dustin W. Demetriou
Syracuse University, Syracuse, NY
Search for other works by this author on:
H. Ezzat Khalifa
H. Ezzat Khalifa
Syracuse University, Syracuse, NY
Search for other works by this author on:
Dustin W. Demetriou
Syracuse University, Syracuse, NY
H. Ezzat Khalifa
Syracuse University, Syracuse, NY
Paper No:
IPACK2011-52004, pp. 395-404; 10 pages
Published Online:
February 14, 2012
Citation
Demetriou, DW, & Khalifa, HE. "Energy Modeling of Air-Cooled Data Centers: Part II—The Effect of Recirculation on the Energy Optimization of Open-Aisle, Air-Cooled Data Centers." Proceedings of the ASME 2011 Pacific Rim Technical Conference and Exhibition on Packaging and Integration of Electronic and Photonic Systems. ASME 2011 Pacific Rim Technical Conference and Exhibition on Packaging and Integration of Electronic and Photonic Systems, MEMS and NEMS: Volume 2. Portland, Oregon, USA. July 6–8, 2011. pp. 395-404. ASME. https://doi.org/10.1115/IPACK2011-52004
Download citation file:
16
Views
Related Proceedings Papers
Related Articles
A Simulation-Based Approach to Data Center Thermal Efficiency Optimization
J. Eng. Sustain. Bldgs. Cities (February,2020)
Experimental and Numerical Analysis of Data Center Pressure and Flow Fields Induced by Backward and Forward CRAH Technology
J. Electron. Packag (September,2022)
Energy Optimization of
Air-Cooled Data Centers
J. Thermal Sci. Eng. Appl (December,2010)
Related Chapters
Control and Operational Performance
Closed-Cycle Gas Turbines: Operating Experience and Future Potential
Optimization of Contact Search Policy in Wireless Mobile Ad Hoc Networks
International Conference on Software Technology and Engineering, 3rd (ICSTE 2011)
The Finite-Differencing Enhanced LCMM
Introduction to Finite Element, Boundary Element, and Meshless Methods: With Applications to Heat Transfer and Fluid Flow