Local airflow distribution in data center environments has historically been accomplished through ventilation tiles distributed over a raised floor air distribution plenum. The tiles are initially configured upon the commissioning of the facility and, as IT equipment configuration changes with time, the tiles are adjusted accordingly. However, tile adjustment is a manual process that is error-prone and often non-intuitive. Tile flow rates are a strong function of under floor plenum pressure distribution which is subject to change as tile layouts are reconfigured. Thermal models are often developed to assist with layout changes, but these models can be time-consuming to generate and require skilled users to achieve accurate results. This paper presents an adaptive vent tile (AVT) for use in raised floor data centers that can adapt to the needs of nearby IT equipment. We present a multi-input-multi-output (MIMO) AVT controller that automatically and dynamically adjusts a multiplicity of AVT openings in coordination such that thermal management requirements are met with minimum use of airflow. We describe the development of dynamic models and algorithm design of the MIMO controller. The controller was evaluated with a set of AVT units in a production data center environment. Results show that the controller can optimize local airflow distribution, provide fine-grained rack intake temperature control and respond to disturbances in a manner that is not achievable through static distribution of tiles.
Skip Nav Destination
ASME 2009 InterPACK Conference collocated with the ASME 2009 Summer Heat Transfer Conference and the ASME 2009 3rd International Conference on Energy Sustainability
July 19–23, 2009
San Francisco, California, USA
Conference Sponsors:
- Electronic and Photonic Packaging Division
ISBN:
978-0-7918-4360-4
PROCEEDINGS PAPER
Local Cooling Control of Data Centers With Adaptive Vent Tiles Available to Purchase
Monem H. Beitelmal,
Monem H. Beitelmal
Hewlett-Packard Laboratories, Palo Alto, CA
Search for other works by this author on:
Zhikui Wang,
Zhikui Wang
Hewlett-Packard Laboratories, Palo Alto, CA
Search for other works by this author on:
Carlos Felix,
Carlos Felix
Hewlett-Packard Laboratories, Palo Alto, CA
Search for other works by this author on:
Cullen Bash,
Cullen Bash
Hewlett-Packard Laboratories, Palo Alto, CA
Search for other works by this author on:
Christopher Hoover,
Christopher Hoover
Hewlett-Packard Laboratories, Palo Alto, CA
Search for other works by this author on:
Alan McReynolds
Alan McReynolds
Hewlett-Packard Laboratories, Palo Alto, CA
Search for other works by this author on:
Monem H. Beitelmal
Hewlett-Packard Laboratories, Palo Alto, CA
Zhikui Wang
Hewlett-Packard Laboratories, Palo Alto, CA
Carlos Felix
Hewlett-Packard Laboratories, Palo Alto, CA
Cullen Bash
Hewlett-Packard Laboratories, Palo Alto, CA
Christopher Hoover
Hewlett-Packard Laboratories, Palo Alto, CA
Alan McReynolds
Hewlett-Packard Laboratories, Palo Alto, CA
Paper No:
InterPACK2009-89035, pp. 645-652; 8 pages
Published Online:
December 24, 2010
Citation
Beitelmal, MH, Wang, Z, Felix, C, Bash, C, Hoover, C, & McReynolds, A. "Local Cooling Control of Data Centers With Adaptive Vent Tiles." Proceedings of the ASME 2009 InterPACK Conference collocated with the ASME 2009 Summer Heat Transfer Conference and the ASME 2009 3rd International Conference on Energy Sustainability. ASME 2009 InterPACK Conference, Volume 2. San Francisco, California, USA. July 19–23, 2009. pp. 645-652. ASME. https://doi.org/10.1115/InterPACK2009-89035
Download citation file:
19
Views
Related Proceedings Papers
Related Articles
Viability of Dynamic Cooling Control in a Data Center
Environment
J. Electron. Packag (June,2006)
Experimental and Computational Investigations of the Thermal Environment in a Small Operational Data Center for Potential Energy Efficiency Improvements
J. Electron. Packag (September,2020)
Experimental and Numerical Analysis of Data Center Pressure and Flow Fields Induced by Backward and Forward CRAH Technology
J. Electron. Packag (September,2022)
Related Chapters
Pulsating Supercavities: Occurrence and Behavior
Proceedings of the 10th International Symposium on Cavitation (CAV2018)
Case Studies
Nonlinear Regression Modeling for Engineering Applications: Modeling, Model Validation, and Enabling Design of Experiments
On the Average Diameter of Directed Double-Loop Networks
International Conference on Instrumentation, Measurement, Circuits and Systems (ICIMCS 2011)