Cray supercomputers are purpose-built to meet the special needs of capability class HPC applications. Recent advances in Cray scalar supercomputer systems resulted in the introduction of the higher density compute cabinet that consumes significant amounts of electrical power and produces an extraordinary amount of heat. Due to the new design requirements, which have tremendous consequences with regard to thermal management, new cooling concepts were required. The XT4 can have up to 30,000 dual-core Opterons, and the SeaStar2 interconnection chip plugs right into the Hyper Transport links on the Opteron processors to make a very fast mesh of processors and memory for applications. Such a machine consumes about 5.2 megawatts of power to deliver around 1.15 petaflops. That is twice the size of Red Storm, but more than a factor of 10 more performance. The extra power density required additional modification to the cooling system. This article describes the design, simulations and verification of the XT-3 and XT-4 systems. Over the past few years thermal design for cooling microprocessors has become increasingly challenging, as silicon technology continues to scale in accordance with Moore’s law. The industry has traditionally relied on gradual improvements in air cooled, solid metal heat sinks to keep pace with change in microprocessor design to provide cost effective solution for removing from microprocessors. In Cray’s XT-4 system, chip power density is expected to almost double that of it’s Red Storm/XT-3 predecessors, while maintaining the same cabinet size.
Skip Nav Destination
ASME 2007 InterPACK Conference collocated with the ASME/JSME 2007 Thermal Engineering Heat Transfer Summer Conference
July 8–12, 2007
Vancouver, British Columbia, Canada
Conference Sponsors:
- Electronic and Photonic Packaging Division
ISBN:
0-7918-4278-9
PROCEEDINGS PAPER
Design and Verification of Cray XT- 4 Supercomputer Cooling System
Alexander Yatskov
Alexander Yatskov
Cray, Inc.
Search for other works by this author on:
Alexander Yatskov
Cray, Inc.
Paper No:
IPACK2007-33336, pp. 437-444; 8 pages
Published Online:
January 8, 2010
Citation
Yatskov, A. "Design and Verification of Cray XT- 4 Supercomputer Cooling System." Proceedings of the ASME 2007 InterPACK Conference collocated with the ASME/JSME 2007 Thermal Engineering Heat Transfer Summer Conference. ASME 2007 InterPACK Conference, Volume 2. Vancouver, British Columbia, Canada. July 8–12, 2007. pp. 437-444. ASME. https://doi.org/10.1115/IPACK2007-33336
Download citation file:
5
Views
Related Proceedings Papers
Related Articles
Air Cooling of Power Electronics Through Vertically Enhanced Manifold Microchannel Systems (VEMMS)
J. Heat Transfer (October,2021)
System-Level Thermal Management and Reliability of Automotive Electronics: Goals and Opportunities Using Phase-Change Materials
J. Electron. Packag (December,2020)
Design and Analysis: Thermal Emulator Cubes for Opto-Electronic Stacked Processor
J. Electron. Packag (September,2002)
Related Chapters
Introduction
Thermal Management of Microelectronic Equipment
Outlook
Closed-Cycle Gas Turbines: Operating Experience and Future Potential
Thermoelectric Coolers
Thermal Management of Microelectronic Equipment