This paper focuses on the effect on inlet rack air temperatures when adjacent racks are removed. Only the above floor (raised floor) flow and temperature distributions were analyzed for various air flowrates exhausting from the perforated tiles and the rack. A Computational Fluid Dynamic (CFD) model was generated for the room with electronic equipment installed on a raised floor with particular focus on the effects on rack inlet temperatures of these high powered racks. The baseline case was with forty racks of data processing (DP) equipment arranged in rows in a data center cooled by chilled air exhausting from perforated floor tiles. The chilled air was provided by four A/C units placed inside a room 12.1 m wide × 13.4 m long. Since the arrangement of the racks in the data center was symmetric only one-half of the data center was modeled. To see the effect of missing racks adjacent to high powered racks various configurations were analyzed. The numerical modeling was performed using a commercially available finite control volume computer code called Flotherm (Trademark of Flomerics, Inc.). The flow was modeled using the k-e turbulence model. Results are displayed to provide some guidance on the design and layout of a data center.
Skip Nav Destination
ASME 2003 International Electronic Packaging Technical Conference and Exhibition
July 6–11, 2003
Maui, Hawaii, USA
Conference Sponsors:
- Electronic and Photonic Packaging Division
ISBN:
0-7918-3690-8
PROCEEDINGS PAPER
Raised Floor Computer Data Center: Effect on Rack Inlet Temperatures When Adjacent Racks Are Removed
Roger Schmidt,
Roger Schmidt
IBM Corporation, Poughkeepsie, NY
Search for other works by this author on:
Ethan Cruz
Ethan Cruz
IBM Corporation, Poughkeepsie, NY
Search for other works by this author on:
Roger Schmidt
IBM Corporation, Poughkeepsie, NY
Ethan Cruz
IBM Corporation, Poughkeepsie, NY
Paper No:
IPACK2003-35240, pp. 481-493; 13 pages
Published Online:
January 5, 2009
Citation
Schmidt, R, & Cruz, E. "Raised Floor Computer Data Center: Effect on Rack Inlet Temperatures When Adjacent Racks Are Removed." Proceedings of the ASME 2003 International Electronic Packaging Technical Conference and Exhibition. 2003 International Electronic Packaging Technical Conference and Exhibition, Volume 2. Maui, Hawaii, USA. July 6–11, 2003. pp. 481-493. ASME. https://doi.org/10.1115/IPACK2003-35240
Download citation file:
6
Views
Related Proceedings Papers
Related Articles
Experimental and Numerical Analysis of Data Center Pressure and Flow Fields Induced by Backward and Forward CRAH Technology
J. Electron. Packag (September,2022)
Experimental and Computational Investigations of the Thermal Environment in a Small Operational Data Center for Potential Energy Efficiency Improvements
J. Electron. Packag (September,2020)
Inviscid and Viscous Numerical Models Compared to Experimental Data in a Small Data Center Test Cell
J. Electron. Packag (September,2013)
Related Chapters
Thermal Design Guide of Liquid Cooled Systems
Thermal Design of Liquid Cooled Microelectronic Equipment
Study on Heat Emission Numerical Simulation and Layout Optimization Concerning Components of Electronic Equipment
International Conference on Mechanical Engineering and Technology (ICMET-London 2011)
Completing the Picture
Air Engines: The History, Science, and Reality of the Perfect Engine