A novel liquid-desiccant air conditioner that dries and cools building supply air has been successfully designed, built and tested. The new air conditioner will transform the use of direct-contact liquid-desiccant systems in HVAC applications, improving comfort and indoor air quality, as well as providing energy-efficient humidity control. Liquid-desiccant conditioners and regenerators are traditionally implemented as adiabatic beds of contact media that are highly flooded with desiccant. The possibility of droplet carryover into the supply air has limited the sale of these systems in most HVAC applications. The characteristic of the new conditioner and regenerator that distinguishes them from conventional ones is their very low flows of liquid desiccant. Whereas a conventional conditioner operates typically at between 10 and 15 gpm (630 and 946 ml/s) of desiccant per 1000 cfm (0.47 m3/s) of process air, the new conditioner operates at 0.5 gpm (32 ml/s) per 1000 cfm (0.47 m3/s). At these low flooding rates, the supply air will not entrain droplets of liquid desiccant. This brings performance and maintenance for the new liquid-desiccant technology in line with HVAC market expectations. Low flooding rates are practical only if the liquid desiccant is continually cooled in the conditioner or continually heated in the regenerator as the mass exchange of water occurs. This simultaneous heat and mass exchange is accomplished by using the walls of a parallel-plate plastic heat exchanger as the air/desiccant contact surface. Compared to existing solid and liquid desiccant systems, the low-flow technology is more compact, has significantly lower pressure drops and does not “dump” heat back onto the building’s central air conditioner. Tests confirm the high sensible and latent effectiveness of the conditioner, the high COP of the regenerator, and the operation of both components without carryover.
Skip Nav Destination
ASME 2006 International Solar Energy Conference
July 8–13, 2006
Denver, Colorado, USA
Conference Sponsors:
- Solar Energy Division
ISBN:
0-7918-4745-4
PROCEEDINGS PAPER
A Zero Carryover Liquid-Desiccant Air Conditioner for Solar Applications
Andrew Lowenstein,
Andrew Lowenstein
AIL Research, Inc., Princeton, NJ
Search for other works by this author on:
Steve Slayzak,
Steve Slayzak
National Renewable Energy Laboratory, Golden, CO
Search for other works by this author on:
Eric Kozubal
Eric Kozubal
National Renewable Energy Laboratory, Golden, CO
Search for other works by this author on:
Andrew Lowenstein
AIL Research, Inc., Princeton, NJ
Steve Slayzak
National Renewable Energy Laboratory, Golden, CO
Eric Kozubal
National Renewable Energy Laboratory, Golden, CO
Paper No:
ISEC2006-99079, pp. 397-407; 11 pages
Published Online:
October 2, 2008
Citation
Lowenstein, A, Slayzak, S, & Kozubal, E. "A Zero Carryover Liquid-Desiccant Air Conditioner for Solar Applications." Proceedings of the ASME 2006 International Solar Energy Conference. Solar Energy. Denver, Colorado, USA. July 8–13, 2006. pp. 397-407. ASME. https://doi.org/10.1115/ISEC2006-99079
Download citation file:
30
Views
Related Proceedings Papers
Related Articles
Development of a New Model of Single-Speed Air Conditioners at Part-Load Conditions for Hourly Simulations
J. Sol. Energy Eng (May,2005)
Open-Cycle Desiccant Air Conditioning as an Alternative to Vapor Compression Cooling in Residential Applications
J. Sol. Energy Eng (August,1984)
Automated Fault Detection and Diagnostics for Vapor Compression Cooling Equipment
J. Sol. Energy Eng (August,2003)
Related Chapters
Examination of Seasonal Energy Efficiency Ratio and Economical Analysis of Room Air Conditioner
Proceedings of the 2010 International Conference on Mechanical, Industrial, and Manufacturing Technologies (MIMT 2010)
Performance Comparison of Air-Cooled and Water-Cooled Air-Conditioners Applied in Residential Buildings
Inaugural US-EU-China Thermophysics Conference-Renewable Energy 2009 (UECTC 2009 Proceedings)
Inside the Building
Geothermal Heat Pump and Heat Engine Systems: Theory and Practice