The traditional chilled water loop has been designed as a primary/secondary (P/S) system for several years. The primary loop maintains constant chilled water flow through the evaporator, and the secondary loop is designed as a variable flow system in response to variations in building cooling load. The primary/secondary design separates the chiller operation from the building load requirements. This design principle has been working adequately for old chillers that require constant chilled water flow to achieve stable chiller performance. However, these chillers operate inefficiently and consume unnecessary pump power. In recent years, the chiller industry has begun the use of variable water flow through evaporators. Significant energy savings can be achieved by using the variable flow principle. This paper compares the P/S system with variable chilled water system and also proposes an innovative solution: chilled water supply temperature reset to maintain the minimum chilled water flow and eliminate by-pass water flow. The energy consumption models including pump power and chiller compressor power improvement are presented to simulate the energy performance of two systems. ASHRAE detailed cooling coil models are also adopted to simulate the cooling coil discharge air humidity in order to verify the impacts of the chilled water supply temperature reset. Finally, a case study building demonstrates experimental results. Up to 10% pump and compressor power saving is demonstrated by simulations and the case study.
Skip Nav Destination
ASME 2005 International Solar Energy Conference
August 6–12, 2005
Orlando, Florida, USA
Conference Sponsors:
- Solar Energy Division
ISBN:
0-7918-4737-3
PROCEEDINGS PAPER
Energy Use and Performance of a New Variable Primary-Flow Chilled Water System
Li Song,
Li Song
Building Energy Solutions & Technology, Inc.
Search for other works by this author on:
Ik-Seong Joo,
Ik-Seong Joo
Building Energy Solutions & Technology, Inc.
Search for other works by this author on:
Mingsheng Liu
Mingsheng Liu
University of Nebraska
Search for other works by this author on:
Li Song
Building Energy Solutions & Technology, Inc.
Ik-Seong Joo
Building Energy Solutions & Technology, Inc.
Mingsheng Liu
University of Nebraska
Paper No:
ISEC2005-76066, pp. 545-553; 9 pages
Published Online:
October 15, 2008
Citation
Song, L, Joo, I, & Liu, M. "Energy Use and Performance of a New Variable Primary-Flow Chilled Water System." Proceedings of the ASME 2005 International Solar Energy Conference. Solar Energy. Orlando, Florida, USA. August 6–12, 2005. pp. 545-553. ASME. https://doi.org/10.1115/ISEC2005-76066
Download citation file:
12
Views
Related Proceedings Papers
Related Articles
Variable Water Flow Pumping for Central Chilled Water Systems
J. Sol. Energy Eng (August,2002)
Importance of Auxiliary Power Consumption for Combined Cycle Performance
J. Eng. Gas Turbines Power (April,2011)
Efficient Operation of Air-Side Economizer Using Extremum Seeking Control
J. Dyn. Sys., Meas., Control (May,2010)
Related Chapters
Control and Operational Performance
Closed-Cycle Gas Turbines: Operating Experience and Future Potential
System Automation
Pipeline Operation & Maintenance: A Practical Approach, Second Edition
CFD Simulations of a Mixed-flow Pump Using Various Turbulence Models
Mixed-flow Pumps: Modeling, Simulation, and Measurements