Detailed temperature and pressure measurements in high aspect ratio parallel plate fin heat sinks were made in a Top Inlet Side Exit (TISE) experiment configuration without top bypass flow. Air flow was supplied to the top of the heat sink using a rectangular jet nozzle with three different jet nozzle widths, Wj. The study covered five jet velocities and three different jet nozzle width to heat sink length ratios. Static pressure measurements were made along the spanwise centerline inside the heat sink and on the mounting plate outside the heat sink. The measurements were used to study the influence of the jet impinging on the top of the heat sink on the loss coefficient of the heat sink. It was found that the overall loss coefficient was dependent on Re, Wj, the fin spacing, b, and the jet nozzle width relative to the heat sink length, Wj/L. Temperature measurements were made to study the total thermal resistance with no base heat spreading. An ad hoc model was used to predict the total thermal resistance of the heat sink in this complicated flow. The model modifies the total cooled area of the fin as a function of jet width and heat sink geometry. Good agreement was found with the experimental data for the cases of Wj/L = 1.0 and 0.5. The model does not work well in the case of Wj/L = 0.25.