This study presents the measurements of R-134a two-phase frictional pressure gradient subject to vertical and horizontal arrangements of a U-type wavy tube with inner diameter of 5.07 mm and a curvature ratio of 5. The ratio between two-phase pressure gradients of U-bend and straight tube is about 2.5 - 3.5. For the straight tube, the frictional two-phase pressure gradient ratio between the vertical and horizontal arrangements is marginally higher (1.0 - 1.2) for annular flow pattern at x > 0.5, and is 1.0 - 1.4 for the U-bend in the wavy tube. The higher resistance in the vertical arrangement is due to the buoyancy force against the flow inertia. However, for x < 0.5, this ratio is gradually increased due to the difference of flow pattern. The ratio is increased to 1.8 in the straight tube. For the U-bend, the ratio is 2.1 for flow entering the upper tube and is 1.5 for flow entering the lower tube at x = 0.1 and G = 200 kg/m2·s. For the vertical wavy tube, additional effects like the flow pattern transition, liquid flow reversal, and freezing slug may cause additional pressure drops.
Skip Nav Destination
ASME 2006 International Mechanical Engineering Congress and
Exposition
November 5–10, 2006
Chicago, Illinois, USA
Conference Sponsors:
- Fluids Engineering Division
ISBN:
0-7918-4770-5
PROCEEDINGS PAPER
Frictional Pressure Drops of Two-Phase R-134A Flow in Horizontal and Vertical U-Type Wavy and Straight Tubes
Ing Youn Chen,
Ing Youn Chen
National Yunlin University of Science and Technology
Search for other works by this author on:
Yu-Shi Wu,
Yu-Shi Wu
National Yunlin University of Science and Technology
Search for other works by this author on:
Yu-Juei Chang,
Yu-Juei Chang
Industrial Technology Research Institute
Search for other works by this author on:
Chi-Chuan Wang
Chi-Chuan Wang
Industrial Technology Research Institute
Search for other works by this author on:
Ing Youn Chen
National Yunlin University of Science and Technology
Yu-Shi Wu
National Yunlin University of Science and Technology
Yu-Juei Chang
Industrial Technology Research Institute
Chi-Chuan Wang
Industrial Technology Research Institute
Paper No:
IMECE2006-13247, pp. 803-809; 7 pages
Published Online:
December 14, 2007
Citation
Chen, IY, Wu, Y, Chang, Y, & Wang, C. "Frictional Pressure Drops of Two-Phase R-134A Flow in Horizontal and Vertical U-Type Wavy and Straight Tubes." Proceedings of the ASME 2006 International Mechanical Engineering Congress and Exposition. Fluids Engineering. Chicago, Illinois, USA. November 5–10, 2006. pp. 803-809. ASME. https://doi.org/10.1115/IMECE2006-13247
Download citation file:
6
Views
0
Citations
Related Proceedings Papers
Related Articles
Correlation of Adiabatic Two-Phase Pressure Drop Data Using the Frictional Law of Corresponding States
J. Fluids Eng (June,1993)
Determination of the Pressure Drop Optimum Pipe Size for a Two-Phase Slug Flow in an Inclined Pipe
J. Eng. Ind (November,1970)
Pressure Drop Correlations for Inclined Two-Phase Flow
J. Energy Resour. Technol (December,1985)
Related Chapters
Introduction
Design and Analysis of Centrifugal Compressors
Boundary Layer Analysis
Centrifugal Compressors: A Strategy for Aerodynamic Design and Analysis
Factors to be Considered
Consensus for the Lay-up of Boilers, Turbines, Turbine Condensors, and Auxiliary Equipment (CRTD-66)