Capacity control in most commercial centrifugal chillers is achieved by inlet guide vanes, which are activated by the leaving chilled water temperature sensor. Due to mechanical reasons, vane control is done discretely, and not continuously. The control module compares the value provided by the temperature sensor to pre-set control band values, and if those bands are exceeded, it sends a signal to the vane control motor to adjust the vane position by one step that could be upwards or downwards. The advantage of this type of discrete control method is its simplicity. Normally, the accuracy in the outlet chilled water temperature is of the order of 0.5°C, which is acceptable for normal cooling plants such as used in office buildings. However, there are applications such as in pharmaceutical processes, mechanics labs, or instances in chemical processes where more accurate control is required (sometimes as low as 0.05°C). This paper proposes a simple method to achieve such tight control without any hardware modifications. The basis of this method is a transient physical inverse model of the refrigerant boiling process in the evaporator, in conjunction with a feed-forward control scheme. The model parameters need to be identified from monitored data since they are chiller-specific. This paper describes the model, and applies it to one-minute monitored data from an actual chiller plant of 1580 kW (450 Tons). It is demonstrated that for this specific chiller such a control scheme has the potential to improve control accuracy by about 28% as compared to the traditional control method.
Skip Nav Destination
ASME 2002 International Mechanical Engineering Congress and Exposition
November 17–22, 2002
New Orleans, Louisiana, USA
Conference Sponsors:
- Advanced Energy Systems Division
ISBN:
0-7918-3626-6
PROCEEDINGS PAPER
A Model-Based Feed-Forward Controller Scheme for Accurate Chilled Water Temperature Control of Inlet Guide Vane Centrifugal Chillers
Yongzhong Jia,
Yongzhong Jia
Drexel University, Philadelphia, PA
Search for other works by this author on:
T. Agami Reddy
T. Agami Reddy
Drexel University, Philadelphia, PA
Search for other works by this author on:
Yongzhong Jia
Drexel University, Philadelphia, PA
T. Agami Reddy
Drexel University, Philadelphia, PA
Paper No:
IMECE2002-33343, pp. 513-522; 10 pages
Published Online:
June 3, 2008
Citation
Jia, Y, & Reddy, TA. "A Model-Based Feed-Forward Controller Scheme for Accurate Chilled Water Temperature Control of Inlet Guide Vane Centrifugal Chillers." Proceedings of the ASME 2002 International Mechanical Engineering Congress and Exposition. Advanced Energy Systems. New Orleans, Louisiana, USA. November 17–22, 2002. pp. 513-522. ASME. https://doi.org/10.1115/IMECE2002-33343
Download citation file:
6
Views
Related Proceedings Papers
Related Articles
A Model-Based Feed-Forward Controller Scheme for Accurate Chilled Water Temperature Control of Inlet Guide Vane Centrifugal Chillers
J. Sol. Energy Eng (February,2005)
On the Development of a Low Cost Pyrheliometer
J. Sol. Energy Eng (August,2011)
Application of Silicon Carbide Photodiode Flame Temperature Sensors in an Active Combustion Pattern Factor Control System
J. Eng. Gas Turbines Power (January,2011)
Related Chapters
Comparison of the Availability of Trip Systems for Reactors with Exothermal Reactions (PSAM-0361)
Proceedings of the Eighth International Conference on Probabilistic Safety Assessment & Management (PSAM)
QP Based Encoder Feedback Control
Robot Manipulator Redundancy Resolution
Evaluating Functional Coupling in Aeration Basin Air Distribution Systems
Advances in Multidisciplinary Engineering