A comprehensive theoretical development, confirmed by inplant measurements, will be summarized showing the dependence of condenser air in-leakage and exhauster capacity on build up of excess back pressure caused by the establishment of a zone of stagnation near the condenser’s air removal section. It has been generally believed that there will not be a zone of stagnation and an associated excess back pressure, above the design pressure, provided the exhauster capacity for air removal remains higher than the air in-leakage regardless of the leakage size. This paper will show, however, that excess back pressure can occur at high air in-leakage, even though exhauster capacity is adequate. A gradual increase in the concentration of non-condensables as steam scavenges these gases toward the air removal section is presented. This results in a reduction of individual tube heat transfer coefficient in the high air concentration region which is accompanied by an increase in condenser pressure. It will be shown that this may be the condition of heat transfer reduction that many authors have used throughout the 20th century to describe the effect of air on all tubes in the condenser. An associated condition will also be discussed related to subcooling of the gas and vapor space between tubes within the region of reduced heat transfer. With high air in-leakage and high exhauster capacity, it will be shown that near the air removal section the large amount of air flow will scavenge steam through the subcooled region, directed toward the vent line, causing generation of a condensate mist that becomes suspended in the moving air. The reported theoretical explanation is derived using a condenser model developed earlier by the author. The results are confirmed from measurement data taken on an operating plant using a RheoVac® condenser performance and diagnostic instrument, the description of which may be found in the open literature.
Skip Nav Destination
International Joint Power Generation Conference collocated with TurboExpo 2003
June 16–19, 2003
Atlanta, Georgia, USA
Conference Sponsors:
- Power Division
ISBN:
0-7918-3692-4
PROCEEDINGS PAPER
On the Inability of Multiple Exhausters to Eliminate Condenser Excess Back Pressure at High Air In-Leakage
Joseph W. Harpster
Joseph W. Harpster
Intek, Inc., Westerville, OH
Search for other works by this author on:
Joseph W. Harpster
Intek, Inc., Westerville, OH
Paper No:
IJPGC2003-40081, pp. 83-90; 8 pages
Published Online:
December 17, 2008
Citation
Harpster, JW. "On the Inability of Multiple Exhausters to Eliminate Condenser Excess Back Pressure at High Air In-Leakage." Proceedings of the International Joint Power Generation Conference collocated with TurboExpo 2003. 2003 International Joint Power Generation Conference. Atlanta, Georgia, USA. June 16–19, 2003. pp. 83-90. ASME. https://doi.org/10.1115/IJPGC2003-40081
Download citation file:
1
Views
Related Articles
Theoretical Modeling of Vapor Condensation in the Presence of Noncondensable Gas on a Horizontal Tube
J. Heat Transfer (December,2019)
Filmwise Condensation From Humid Air on a Vertical Superhydrophilic Surface: Explicit Roles of the Humidity Ratio Difference and the Degree of Subcooling
J. Heat Transfer (June,2021)
The Condensation of Ammonia-Water Mixtures in a Horizontal Shell and
Tube Condenser
J. Heat Transfer (August,2004)
Related Chapters
Combined Cycle Power Plant
Energy and Power Generation Handbook: Established and Emerging Technologies
Lay-Up and Start-Up Practices
Consensus on Operating Practices for Control of Water and Steam Chemistry in Combined Cycle and Cogeneration
Outlook
Closed-Cycle Gas Turbines: Operating Experience and Future Potential