One of the challenges in the production of electricity is the cooling water management because the calcium content in circulating cooling water continues to increase with time as pure water evaporates. Thus, the excessive mineral contents in water circulation systems could cause severe fouling in heat transfer equipment. To avoid the catastrophic failure in condensers, the cooling water is discharged after 3 cycles at a rate of 10 million gallons a day in a 1,000-MW thermoelectric power plant. The present study investigated the effect of pulsed spark discharges on the mitigation of mineral fouling in a concentric counterflow heat exchanger. Artificial hard water with calcium carbonate hardness ranging from 250 to 500 ppm was used with velocity varying over a range of 0.1–0.5 m/s and zero blowdown. Fouling resistances decreased by 50–88% for the plasma treated cases compared with the values for no-treatment cases. SEM photographs showed particle with larger sizes for the plasma treated cases comparing to smaller but more organized particles for the no-treatment cases. The different structures of particles were associated with pulsed spark discharge assisted precipitation of calcium carbonate in oversaturated hard water. X-ray diffraction data showed calcite crystal structures for all cases.
Skip Nav Destination
2010 14th International Heat Transfer Conference
August 8–13, 2010
Washington, DC, USA
Conference Sponsors:
- Heat Transfer Division
ISBN:
978-0-7918-4939-2
PROCEEDINGS PAPER
Application of Pulsed Spark Discharge for Mitigation of Mineral Fouling in a Heat Exchanger
Hyoungsup Kim,
Hyoungsup Kim
Drexel University, Philadelphia, PA
Search for other works by this author on:
Jin M. Jung,
Jin M. Jung
Drexel University, Philadelphia, PA
Search for other works by this author on:
Alexander Fridman,
Alexander Fridman
Drexel University, Philadelphia, PA
Search for other works by this author on:
Young I. Cho
Young I. Cho
Drexel University, Philadelphia, PA
Search for other works by this author on:
Yong Yang
Drexel University, Philadelphia, PA
Hyoungsup Kim
Drexel University, Philadelphia, PA
Jin M. Jung
Drexel University, Philadelphia, PA
Alexander Fridman
Drexel University, Philadelphia, PA
Young I. Cho
Drexel University, Philadelphia, PA
Paper No:
IHTC14-22392, pp. 385-393; 9 pages
Published Online:
March 1, 2011
Citation
Yang, Y, Kim, H, Jung, JM, Fridman, A, & Cho, YI. "Application of Pulsed Spark Discharge for Mitigation of Mineral Fouling in a Heat Exchanger." Proceedings of the 2010 14th International Heat Transfer Conference. 2010 14th International Heat Transfer Conference, Volume 4. Washington, DC, USA. August 8–13, 2010. pp. 385-393. ASME. https://doi.org/10.1115/IHTC14-22392
Download citation file:
9
Views
Related Proceedings Papers
Removal of Calcium Carbonate Build-Up in Condenser Tubes Restores Efficiency
POWER2017-ICOPE-17
Related Articles
Mineral Fouling Control by Underwater Plasma Discharge in a Heat Exchanger
J. Heat Transfer (May,2011)
Simulation and Experimental Analysis of a Solar Driven Absorption Chiller With Partially Wetted Evaporator
J. Sol. Energy Eng (February,2010)
Related Chapters
Engineering and Physical Modeling of Power Plant Cooling Systems
Thermal Power Plant Cooling: Context and Engineering
Threshold Functions
Closed-Cycle Gas Turbines: Operating Experience and Future Potential
Introduction
Thermal Power Plant Cooling: Context and Engineering