The efficient cooling of servers in data center offers unique challenge to reduce the worldwide energy consumption and fluid inventory. The presented work addresses the great potential of a thermosiphon system using two-phase heat transfer process which improves the efficiency of the system by significantly improving the heat dissipation ability. The latent heat transfer is more effective than sensible heat. However, the system performance is limited by Critical Heat Flux (CHF) and Heat Transfer Coefficients (HTC). An increase in CHF offers wide temperature operating range while HTC defines the efficiency of the process. In the current design of the cooling solution, a manifold with a taper is employed over the heater surface to guide vapor away from the surface along the flow length. The incoming liquid flows over the heating surface unobstructed developing separate liquid-vapor pathways. A 6° taper manifold is analyzed with HFE7000 as the working fluid. The performance of thermosiphon loop is evaluated for three different liquid volumes resulting in three different liquid heads available in the thermosiphon loop. The respective heat flux and HTC are compared. The maximum heat dissipation was observed for 325ml liquid with a microchannel chip resulting in a CHF of 42.1W/cm2 at a wall superheat of 17.8°C. The observed performance data shows that thermosiphon loop is an eligible replacement for conventional single-phase cooling techniques used for CPU cooling in data centers.
Skip Nav Destination
ASME 2017 15th International Conference on Nanochannels, Microchannels, and Minichannels
August 27–30, 2017
Cambridge, Massachusetts, USA
Conference Sponsors:
- Fluids Engineering Division
ISBN:
978-0-7918-5830-1
PROCEEDINGS PAPER
Effect of Liquid Volume on Thermosiphon Loop Performance Using Open Microchannels Manifold for CPU Cooling in Data Center
Aranya Chauhan,
Aranya Chauhan
Rochester Institute of Technology, Rochester, NY
Search for other works by this author on:
Satish G. Kandlikar
Satish G. Kandlikar
Rochester Institute of Technology, Rochester, NY
Search for other works by this author on:
Aranya Chauhan
Rochester Institute of Technology, Rochester, NY
Satish G. Kandlikar
Rochester Institute of Technology, Rochester, NY
Paper No:
ICNMM2017-5529, V001T05A002; 5 pages
Published Online:
November 10, 2017
Citation
Chauhan, A, & Kandlikar, SG. "Effect of Liquid Volume on Thermosiphon Loop Performance Using Open Microchannels Manifold for CPU Cooling in Data Center." Proceedings of the ASME 2017 15th International Conference on Nanochannels, Microchannels, and Minichannels. ASME 2017 15th International Conference on Nanochannels, Microchannels, and Minichannels. Cambridge, Massachusetts, USA. August 27–30, 2017. V001T05A002. ASME. https://doi.org/10.1115/ICNMM2017-5529
Download citation file:
74
Views
Related Proceedings Papers
Related Articles
High-Flux Thermal Management With Supercritical Fluids
J. Heat Transfer (December,2016)
Embedded Two-Phase Cooling of High Flux Electronics Via Press-Fit and Bonded FEEDS Coolers
J. Electron. Packag (September,2018)
Experimental Characterization of Two-Phase Cold Plates Intended for High-Density Data Center Servers Using a Dielectric Fluid
J. Electron. Packag (June,2021)
Related Chapters
Pool Boiling
Thermal Management of Microelectronic Equipment, Second Edition
Thermal Design Guide of Liquid Cooled Systems
Thermal Design of Liquid Cooled Microelectronic Equipment
Scope of Section I, Organization, and Service Limits
Power Boilers: A Guide to the Section I of the ASME Boiler and Pressure Vessel Code, Second Edition