Data centers play an important role in modern business. They require a large amount of electricity and cooling energy simultaneously. In 2007, the percentage of total energy consumed by data centers in total US energy doubled over seven years and it is estimated to be double again by 2012. Currently data centers typically employ separate cooling, heating and power (SCHP) systems. The Combined Cooling Heating and Power (CCHP) system is an efficient, clean, and reliable approach to generating power and thermal energy from a single fuel source simultaneously on site. They could be suitable energy supply systems for data centers since demands from data centers match with the energy generation of the CCHP systems. This paper assesses the energy performance of a CCHP system for the Qualcomm data center in San Diego, California, by means of modeling and operational data analysis. The CCHP system mainly consists of four gas turbines, one exhaust fired absorption chiller, three hot water fired absorption chillers, three electrical chillers and seven cooling towers. System performance models have been developed and validated by experimental data in TRNSYS. The modeling result shows that the CCHP system is capable of meeting the electricity and cooling demands with an overall system efficiency of 46%. As a result, the CCHP system could approximately save 12.9GWh of energy per year compared with SCHP systems. Therefore, the CCHP system is a sustainable and green option for data centers.
Skip Nav Destination
ASME 2012 6th International Conference on Energy Sustainability collocated with the ASME 2012 10th International Conference on Fuel Cell Science, Engineering and Technology
July 23–26, 2012
San Diego, California, USA
Conference Sponsors:
- Advanced Energy Systems Division
- Solar Energy Division
ISBN:
978-0-7918-4481-6
PROCEEDINGS PAPER
Energy Performance Analysis of a Combined Cooling Heating and Power System for a Data Center
Donghao Xu,
Donghao Xu
Purdue University, West Lafayette, IN
Search for other works by this author on:
Ming Qu
Ming Qu
Purdue University, West Lafayette, IN
Search for other works by this author on:
Donghao Xu
Purdue University, West Lafayette, IN
Ming Qu
Purdue University, West Lafayette, IN
Paper No:
ES2012-91427, pp. 203-208; 6 pages
Published Online:
July 23, 2013
Citation
Xu, D, & Qu, M. "Energy Performance Analysis of a Combined Cooling Heating and Power System for a Data Center." Proceedings of the ASME 2012 6th International Conference on Energy Sustainability collocated with the ASME 2012 10th International Conference on Fuel Cell Science, Engineering and Technology. ASME 2012 6th International Conference on Energy Sustainability, Parts A and B. San Diego, California, USA. July 23–26, 2012. pp. 203-208. ASME. https://doi.org/10.1115/ES2012-91427
Download citation file:
15
Views
Related Proceedings Papers
Related Articles
Design of a Multigenerational System With Absorption Cooling for a Residential Community: A Case Study
J. Energy Resour. Technol (June,2021)
Compact Diesel Engine Waste-Heat-Driven Ammonia–Water Absorption Heat Pump Modeling and Performance Maximization Strategies
J. Energy Resour. Technol (June,2022)
From Chip to Cooling Tower Data Center Modeling: Influence of Server Inlet Temperature and Temperature Rise Across Cabinet
J. Electron. Packag (March,2011)
Related Chapters
Introduction
Consensus on Operating Practices for Control of Water and Steam Chemistry in Combined Cycle and Cogeneration
Scope of Section I, Organization, and Service Limits
Power Boilers: A Guide to the Section I of the ASME Boiler and Pressure Vessel Code, Second Edition
Basics of Hydraulic Loops
Hydraulics, Pipe Flow, Industrial HVAC & Utility Systems: Mister Mech Mentor, Vol. 1