Commissioning services have proven successful in reducing building energy consumption, but the optimal energy performance obtained by commissioning may subsequently degrade. Automated Building Commissioning Analysis Tool (ABCAT), which combines a calibrated simulation with diagnostic techniques, is a simple and cost efficient tool that can help maintain the optimal building energy performance after building commissioning. It can continuously monitor whole building energy consumption, warn operation personnel when an HVAC system problem has increased energy consumption, and assist them in identifying the possible cause(s) of the problem. This paper presents the results of a retrospective implementation of ABCAT on five buildings, each of which has at least three years of post-commissioning daily energy consumption data, on the Texas A&M University campus. The methodology of ABCAT is reviewed and the implementation process of ABCAT on one building is specifically illustrated. Eighteen faults were detected in 15 building-years of consumption data with a defined fault detection standard. The causes of some of the detected faults are verified with historical documentation. The remaining fault diagnoses remain unconfirmed due to data quality issues and incomplete information on maintenance performed in the buildings.
Skip Nav Destination
ASME 2009 3rd International Conference on Energy Sustainability collocated with the Heat Transfer and InterPACK09 Conferences
July 19–23, 2009
San Francisco, California, USA
Conference Sponsors:
- Advanced Energy Systems Division and Solar Energy Division
ISBN:
978-0-7918-4890-6
PROCEEDINGS PAPER
Retrospective Testing of an Automated Building Commissioning Analysis Tool (ABCAT)
Guanjing Lin,
Guanjing Lin
Texas A&M University, College Station, TX
Search for other works by this author on:
David E. Claridge
David E. Claridge
Texas A&M University, College Station, TX
Search for other works by this author on:
Guanjing Lin
Texas A&M University, College Station, TX
David E. Claridge
Texas A&M University, College Station, TX
Paper No:
ES2009-90040, pp. 229-236; 8 pages
Published Online:
September 29, 2010
Citation
Lin, G, & Claridge, DE. "Retrospective Testing of an Automated Building Commissioning Analysis Tool (ABCAT)." Proceedings of the ASME 2009 3rd International Conference on Energy Sustainability collocated with the Heat Transfer and InterPACK09 Conferences. ASME 2009 3rd International Conference on Energy Sustainability, Volume 2. San Francisco, California, USA. July 19–23, 2009. pp. 229-236. ASME. https://doi.org/10.1115/ES2009-90040
Download citation file:
8
Views
Related Proceedings Papers
Related Articles
Controls and Diagnostics for Air Distribution Systems
J. Sol. Energy Eng (August,2003)
Bringing Automated Fault Detection and Diagnostics Tools for HVAC&R Into the Mainstream
J. Eng. Sustain. Bldgs. Cities (August,2020)
An Innovation-Based Methodology for HVAC System Fault Detection
J. Dyn. Sys., Meas., Control (December,1985)
Related Chapters
An Energy-Efficient Smart Building with or without the Cooperation of Its Occupants?
Smart Users for Energy and Societal Transition
The Design and Implement of Remote Inclinometer for Power Towers Based on MXA2500G/GSM
International Conference on Mechanical and Electrical Technology, 3rd, (ICMET-China 2011), Volumes 1–3
Automated Fault Detection and Diagnosis in HVAC Systems
Handbook of Integrated and Sustainable Buildings Equipment and Systems, Volume I: Energy Systems